The City of Chicago developed and utilizes its own building code which contains
all the provisions for the construction, alteration, and operation of a building. The Chicago
Building Code includes chapters on fire protection, electrical systems, mechanical
systems, plumbing systems, and means of egress for new construction and the operation
of existing buildings. Some chapters reference other national consensus standards such
as NFPA, UL and ASTM. However, it is rare that adoption of the entire referenced
document is made by the Code. Rather, sections or some of the details on installation
might be referenced.
The City of Chicago Building Code would define the storage of records as a Class
H-2, Moderate Hazard Storage. A code complying “Standard Sprinkler System” (as
defined by the Code) would have been required. These requirements would most likely
have specified an ordinary hazard automatic sprinkler system that would have roughly
complied with a pre-1990 edition of NFPA Standard No. 13. The Code does not clearly
address the need for automatic sprinklers within the storage racks nor under the open
grate style catwalks in this occupancy. The Chicago Building Code does not explicitly
reference other NFPA Standards on rack storage or other storage methods exceeding the
heights provided within NFPA Standard No. 13, which is 12 feet.
NFPA No. 232A, Guide for Fire Protection for Archives and Records Centers,
provides information on the protection of large collections of semicurrent records and
specifically includes record centers such as this one. The scope of this document does
not include the storage of important documents that need to be in vaults or special containers
or the storage of cellulose nitrate film. All other types of record media are within
the scope of NFPA No. 232A. In a records center, almost all of the records and their
common storage containers are combustible and will contribute to fire spread and fire
duration. Fire severity is estimated at approximately 1 hour for each 10 pounds per
square foot of combustibles stored (records and containers).
The guide provides a review and comparison of several fire detection and extinguishing
systems. It cautions against the dependence on all forms of fire detection with
manual suppression because of the typical fire development time. Testing with open
shelf storage, fourteen feet high, suggests that in about three minutes the fire can exceed
possible control by portable fire extinguishers. Automatic sprinklers are described as the
most effective and economical fire control measure. NFPA Standard No. 13 is used as
the reference document for installation. The height and method of storage in this case
exceeded the scope of this standard and would suggest the use of other automatic sprinkler
standards.
In addition to automatic sprinklers, NFPA No. 232A describes the use of high
expansion foam, Halon 1301, and carbon dioxide extinguishing systems. The use of high
expansion foam may be effective based on testing done in 1966 and referenced in NFPA
No. 232A. Protection of records centers by Halon would have been very expensive and
this agent is no longer available because of environmental problems. There are limitations
and personnel hazards associated with the use of carbon dioxide. Neither Halon nor
carbon dioxide will always extinguish a deep seated fire within stored records. In addition
both agents are expensive to install and maintain. Similar limitations exist for the
Halon replacement agents.
The use of tall racks with grated intermediate walkways is not recommended by
NFPA No. 232A. Rather, full floors with fire resistance ratings are recommended to limit
the extension of fire travel and to reduce the number of records subject to destruction or
damage in a single fire. Where tall storage racks are used, cautions on fire detection,
complete automatic sprinkler protection, and fire department preplanning are provided.
Preplanning should include how to gain access to the racks, smoke and heat venting from
the fire area, reaching the fire in the upper area, and fighting the fire at its source.
The automatic sprinklers installed at the ceiling were inadequate for the hazard
and did not comply with NFPA Standards. Because of the solid shelves, it is likely that
sprinklers should have been provided at each shelf level. The narrow aisles may have
justified the use of automatic sprinklers along the rack face to slow the fire spread on the
face and between racks.
Next » Lessons Learned